Maxivolt engineers designed the ICP-Series to provide sensitive individual circuit protection. The ICP Plus, ICP-CRA, and 420-RW were later introduced to expand the application and communication versatility of the line. ICP devices require a standard octal 8-pin base to install, are available in series and parallel configurations, and provide an alarm pin for device status monitoring. ICP Plus and ICP-CRA devices provide dry contacts for device status monitoring. All ICP-Series devices feature a hybrid circuit consisting of only the highest quality components engineered to provide an industry best clamping threshold for the specific voltage application they are designed for. Safety fusing and the non-ground dependent design eliminate safety risks associated with competitive devices. The various benefits of ICP-Series products provide clients with a quantifiable payback.

THE 420-RW

  • Hybrid Circuit Surge Suppression
  • Safety Fusing
  • Dual Means of Indication
  • Open Air PCB Construction
  • Low Clamping Voltage
  • Low Surge Current Rating
  • RoHs Compliant

APPLICATION

Voltage

24 DC

Configuration

4-20 mA

CHARACTERISTICS

Fusing

n/a

Indication

Signal Loss

Markings

Permanently Label

Enclosure

1-DIN ABS (UL 94 V-0)

Environmental

RoHS

DIAGRAM

SPECIFICATIONS

Lines

4 + Ground

Nominal Voltage

24v DC

Input V Limit

90v DC

Equipment V Limit

33v DC

Series Resistance

10 Ohms

Operating Temperature

-40° C to 85° C

Operating Humidity

1% to 95%

Stages of Protection

3

Component Response Time

< 1 ns

STANDARD INSTALLATION SUMMARY

Install According To Instructions Provided With Device

  1. Mount 420-RW to DIN rail.
  2. Connect unprotected conductors.
  3. Connect corresponding protected conductors.
  4. Repeat steps 2 and 3 if protecting 2 loops. 
  5. Connect ground conductor.

 

MAXIVOLT
Serious Surge Protection®
ICP Series
Made in the USA

We'd love to hear from you

Contact Us

A team of power quality specialist to help you find a solution for your power quality issues. With vast experience and knowledge protecting industries from transient voltage, our team will help you with product selection, placement, and installation are critical to the performance of a surge protection system.

Send us a Message

logo
Weather Aware
loader-image
Amarillo, US
4:56 am, April 27, 2024
weather icon 58°F
L: 58° H: 58°
scattered clouds
Humidity 21 %
Pressure 1001 mb
Wind 13 mph SSW
Wind Gust: 29 mph
UV Index: 0
Precipitation: 0 inch
Visibility: 10 km
Sunrise: 6:59 am
Sunset: 8:29 pm

Phone

1-800-583-4773

Email

info@maxivolt.com